Specification

Specification

MEDICAL TYPE COPPER PIPE INSTALLATION SPECIFICATION

MEDICAL TYPE COPPER PIPE INSTALLATION SPECIFICATION

MedikalGaz34 18/06/2019 0
MEDICAL TYPE COPPER PIPE INSTALLATION SPECIFICATIONCopper pipes according to EN 1057 World Quality and / or It should be produced according to TSE 380.There should be seamless semi-hard annealed and straight pipe.Copper should be electrolytic and free of arsenic.The inside of the copper pipes must be washed with Trichoterylene or Carbon tetrachloride. The relevant standard, the name of the manufacturer and the suitability for the use of oxygen must be permanently inscribed on the copper pipes.The copper pipes should be closed to the construction site and lowered in nylon packaging.Clamps to be...
Read More
MEDICAL AIR POWER PLANT TECHNICAL SPECIFICATIONS

MEDICAL AIR POWER PLANT TECHNICAL SPECIFICATIONS

MedikalGaz34 18/06/2019 0
MEDICAL AIR POWER PLANT TECHNICAL SPECIFICATIONSThe plant is equipped with the necessary equipment to deliver dry, clean and oil-free air to the hospital system. In case of failure of one of the central compressors, each of them shall be composed of at least two compressors, each of which shall meet the hospital needs. The connections between the Pipeline and the compressors must be made with flexible hose connections in order not to reflect the vibration in the compressor to the hospital line. The ends of the hose connections must be pressed and the connection elements at their ends must be p...
Read More
MEDICAL VACUUM PLANT TECHNICAL SPECIFICATIONS

MEDICAL VACUUM PLANT TECHNICAL SPECIFICATIONS

MedikalGaz34 18/06/2019 0
MEDICAL VACUUM PLANT TECHNICAL SPECIFICATIONS Vacuum power plant The basic elements of the central station, designed for the consumption capacity of the hospital, and the related technical specifications shall be as follows; *** The basic elements forming the central station should be composed of at least the following units. Vacuum Pumps Bacteria Filter group Vacuum Tank Electrical Control Panel with Digital Display Vacuum manometer and other fittings should be.Vacuum pumps should be designed to provide 580 mm / Hg vacuum pressure in the system with the required vacuum flow rate as a result o...
Read More
TECHNICAL SPECIFICATIONS FOR AZOTPROTOXIDE POWER PLANT

TECHNICAL SPECIFICATIONS FOR AZOTPROTOXIDE POWER PLANT

MedikalGaz34 18/06/2019 0
TECHNICAL SPECIFICATIONS FOR AZOTPROTOXIDE POWER PLANTThe system should consist of units that will send the high pressure coming from the tubes to the hospital installation by decreasing the pressure to the hospital Azotprotoxide line. At least 1 year of maintenance and 5 years fee for the system parts must be given a guarantee of availability and this guarantee must be delivered by the company to the hospital management with an official document or letter.There should be a fully automatic control panel which can be fixed in two-part place or wall mounted in the nitrogen protoxide plant. or li...
Read More
OXYGEN POWER PLANT TECHNICAL SPECIFICATIONS

OXYGEN POWER PLANT TECHNICAL SPECIFICATIONS

MedikalGaz34 18/06/2019 1
OXYGEN POWER PLANT TECHNICAL SPECIFICATIONSThe system should consist of units that will send the high pressure coming from the Tubes or Liquid Oxygen plant to the Hospital installation by reducing the pressure to the Hospital Oxygen line. At least 1 year of maintenance and 5 years fee for the system parts must be given a guarantee of availability and this guarantee must be delivered by the company to the hospital management with an official document or letter.There must be a fully automatic control panel which can be fixed in two-part place or wall mounted in the oxygen plant. The upper part o...
Read More